Products

Industrial Centrifugal Fan
Tunnel Fan & Metro Fan
(Gas Heating) Make-up Air Unit
Infrared Radiant Heaters
Mixed Flow Fan
Axial Flow Fan
Inducing Fan
Kitchen Fume Extractor Fan
Cabinet Fans
Inline Centrifugal Fan
Roof Fan
Wall Mounted Fan
AHU FAN
INFINAIR motors
OEM Customization
Intelligent Control

Contact Us

Tel:+86 21-3918 5688 EXT-6896
E-mail:[email protected]

Products

high Efficient Fully Mixed Flow Fan-Wheel Type T-YFIMT

● Wheel Specification: 400~900
● Application: general gas supply and exhaust, positive pressure air supply, Smoke removal duty
● drive type: direct drive
● Installation: hanging, floor-mounted, Outdoor roof
 
● Volume range: 80,000 m³/h
● Static pressure range: 2,150 Pa
● Patented fully mixed flow whee: Balance quality grade up to G2.5
● Advantages of direct drive: efficient, maintenance-free
● Multi-angle selection: More precise selection

Inquiry Online

Fully mixed flow: completely surpass the time of semi mixed flow
1. Revolutionary breakthrough: impellers with front disc, achieving real fully mixed flow
2. Full-process control over flow passage to improve aerodynamic characteristics
3. Optimized design of CFD flow field simulation
4. Inlet Venturi tube: streamlined design
5. Dome-shaped hub: greatly reduce turbulent flow and backflow

Effect of fully mixed flow:
1. Greatly improve the efficiency than traditional semi mixed flow
2. Wide performance range of high efficiency
3. Optimal for medium-pressure inline fans
4. INLINE SUPER-E TM

Characteristics of fully mixed flow wheel- type T

1. Higher static pressure
2. Reduce the loss of air volume caused by system deviation
3. Selection speed lower in the same condition
4. Reduce the vibration and noise further

Multi-angle selection

1. 400-1120mm, a total of 10 kinds of impeller specifications
2. 30-40 angle, a total of 6 kinds of blade angles
3. 4/6poles, a total of 2 kinds speed
4. More precise selection to reduce risk

Advanced process
1. Inlet Venturi tube: spinning process to ensure streamline aerodynamic characteristics
2. Inlet Venturi tube: completely substitute cone, ensuring smooth air flow
3. Front disc: spinning process to ensure streamline aerodynamic characteristics
4. Blade: dedicated fixture to ensure precise welding positioning
5. Hub: dome shaped, with obvious cowling effect
6 Balance quality grade up to G2.5

Outlet straightening vanes
1. Get the swirl flow behind the blade to be smoother
2. Guide the air flow to move axially, reducing turbulent flow
3. Convert partial dynamic pressure to static pressure
4. Improved aerodynamic performance and efficiency of static pressure
5. Effectively reduce the noise

Feature

Optimal selection for inline fan in mid-pressure
1. Compared with inline centrifugal fan: higher efficiency
2. Compared with inline axial fan: higher pressure
3. Between Point A and Point B, high efficiency and low noise
4. Multi-angle for selection coverage completely within the range of shadow area
5. Perfect sound quality: low-frequency and quieter operation
6. Low noise because of fully flow wheel’s aerodynamic physical design
7. Low-frequency characteristic (62.5~250Hz), quieter in people’s ears
8. Double isolation motor’s noise by independent motor chamber

Advantages of direct drive: efficient, maintenance-free
1. Higher transmission efficiency
2. No wearing parts, low maintenance
3. Easier and more effective servicing and maintenance
4. Sealed self-lubricating bearing for motor, increasing service life
5. Compact design to save installation space

Complete functions
1. General air supply& exhaust
2. Smoke removal duty, positive pressure air supply, fire certification
3. Two-speed supply& exhaust
4. Laboratory exhaust

Convenient and flexible installation
1. Floor-mounted: horizontal or vertical
2. Ceiling-mounted: horizontal or vertical
3. Rooftop: Outdoor roof installation with flag-cloud wing band

INFI-KOAT Molecular FilmTM: long-lasting coating

1. Pickling, phosphating and caustic washing to ensure clean surface
2. Electrostatic incorporation of solid powder to obtain uniform coating
3. High-adhesion film melt within high temperature furnace
4. Resistance to ultraviolet, moisture and marine climate
5. Resistance to large area of uniform corrosion and local pitting corrosion

Tech Spec

Section I: Fan type
The fan shall be fully mixed-flow fan equipped with fully mixed-flow wheel, The drive type shall be direct drive. The fan adopts the whole mixed flow impeller with different blade angles to meet the need of optimizing the type selection. Impeller material of carbon steel, must be equipped with front coil and hemisphere hub, straight blade. Impeller should be static and dynamic balance, to achieve the G2.5 standard AMCA204 balance level.

Section I I: Quality standards
Fan shall be tested relevant certifcation according to the No.210 and No.300 Standards of the Air Movement and Control Association (AMCA). The manufacturer shall pass the ISO9001-2008 certification.

Section III: Fan Structure
The fan shall be equipped with streamlined inlet Venturi tube, with straightening vanes mounted within the cylinder to reduce turbulent flow and improve efficiency.
Fan cynlinder: double-layer structure shall be adopted for the fan cylinder, i.e., straightening inner cylinder and straightening vanes shall be configured, and the straightening inner cylinder shall be connected with the inner wall of the outer cylinder thorugh the straightening blade, which can both secure the straightening cylinder and improve the aerodynamic performance of the fan and the efficiency of static pressure; smoother air flow is required; and the blades of the straightening vanes shall be of 3D curved surface in compliance with flow field characteristics.

Section IV: Fan materials
The cylinder and impeller of the fan shall be continuously welded and made of quality carbon steel no less than 2mm thick to ensure the long-term safe and reliable use of the fan.

Section V: Coating

Fan surface shall be polished and cleaned up to remove particulates, welding slag, burrs, sharp edge, iron, oil, then epoxy coating [options: colour changes are available], fan surface shall be free of sags, wrinkle, blisters, exposed metal or peeling after coating. It shall be no corrosion and rust at least 10 years in allowable working condition.

Section VI: Driving Type
The fan impeller shall be directly connected with the motor. The motor shall adopt B5 installation structure, and its protection grade shall be IP54, while insulation class F and temperature rise B. The motor bearing shall be self-lubricating ball bearing. The motor shall be within the straightening cylinder and isolated from the air flow to prevent the effect of the conveying medium on the motor performance; the power reserve coefficient of the motor shall be per 110% so as to improve the safety in using the motor.

Junction box of motor: Since the motor is within the fan, the supplier shall provide junction boxes to lead the wire out of the fan, and correct types of junction boxes shall be selected according to the specific applications, such as fire protection type and common type.

Section VII: Options
Accessories should be provided according to the specific requirements of each equipment. such as air volume control valve, gravity check air valve, vibration isolators, protection net for inlet and outlet, and flexible joints for inlet and outlet, etc.

Section VIII: Fire fighting Certification (Only for smoke removal duty)
The fan shall be tested OK in complying with the General Usage Axial Fan technical Specification (China National Standard JB/T 10562-2006). A test report issued by licensed authorities shall be provided. The fan must be tested according to China National Standard GA 211-2009, Fire Fighting Smoke Removal Fan High Temperature Testing Method, running continuously over 30 minutes when the main duct air temperature is 280 degrees centigrade. The high temperature resistance character must be qualified by presenting an official certificate.

Section IX: Nameplate

Permanently fixed aluminum nameplate shall be fixed on fan body clearly display fan mark, product model and serial number (i.e.: unique ID for each fan), so that the customer can use this number to find out the parts used.

Section X: Acceptable Manufacturers
Qualified suppliers shall have an AAA credit rating. Providing INFINAIR or similar products, with their design based on YFIMT models of INFINAIR.

Online Message